DPOE™ Power System User Manual Part Number: PN380C
Butt splices connectors
Power connector
housing with wire leads
48VDC
Supply
Power Connector on rear side of
DP
OE™ Power Patch Panel or
Compact 8 Midspan
Connector
pinouts
Figure 4: Connecting to a DPoE™ Power Patch Panel or Compact 8 Midspan
NOTE:
The included power harness has two wires for the A-feed power only (pins 1 & 2).
The DP
OE™ Power Patch Panel or Compact 8 Midspan supports an optional
redundant B-feed power option, but the terminals and wire leads are not attached to
the power harness.
Contact PANDUIT Technical Support for more information about connecting the
redundant B-Feed power. (PANDUIT part # DPOEPWRDUAL should be used for
redundant powering options)
WARNING:
The power supply connections on the DP
OE™ Power Patch Panel and the
Compact 8 Midspan are polarized. They will not function if power is wired
improperly.
Table 5: Minimum Recommended DC AWG for 90°C Cabling for Unprotected
Outputs
Total Rectifier Current Rating (A)
Wire and Lug Gauge
(AWG) using 90° C wire
(NEC Table 310.16)
1
10 16
20 14
25 12
1
Table 310.16 uses Table 3B – Sizes of Conductors from BS EN 60950:2000, “Safety of Information
Technology Equipment,” December 2000 for non-building wiring.